Fire Control Coating Systems

Intumescent Coatings Specifications

Fire Ratings

MDF and Timber Clear Finish ( AS 1530-30): Down load Flame control guide

One Coat 165 Sealer (Data sheet)

Apply a single coat of clear sealer varnish at 9 square meters per litre.

Three Coat 166 Intumescent Clear (Data sheet)

Three brushed or rolled coats of 112 microns wet film thickness ( 9 square meters per litre is required to achieve a total of 155 microns dry film thickness for certification or two sprayed coats of 166 microns wet film thickness ( 6 square meters per litre) to achieve certification.

Two Coat 167 protective Topcoat (Data sheet)

The 167 two coat system is required for wet areas and high traffic areas where wash ability durability and film hardness is required.

 

Structural Steel Load Bearing (30;60;90min)

One coat of Corroless QD (Data sheet)

Steel Guard FM (Data sheet)

For a costing on this system please contact one of our technical representatives