Fire Control Coating Systems
Intumescent or Fire Rated Coating Specifications
|
Down load Protective Paints Document for Fire Ratings and Paint Systems...required normally by councils and governing bodies Timber Clear Coating (Tested to AS/NZ 1530-3): Down load Flame guide for system1 (Clear intumecent coating on timber) One Coat 165 Sealer (Data sheet) Apply a single coat of clear sealer varnish at 9 square meters per litre. Three Coat 166 Intumescent Clear (Data sheet) Three brushed or rolled coats of 112 microns wet film thickness ( 9 square meters per litre is required to achieve a total of 155 microns dry film thickness for certification or two sprayed coats of 166 microns wet film thickness ( 6 square meters per litre) to achieve certification. Two Coat 167 protective Topcoat (Data sheet) The 167 two coat required for wet areas and high traffic areas Structural Steel Load Bearing (30;60;90min) One coat of Corroless QD (Data sheet)
|